Manufacturer: Hipotronics
Model: 2293

Hipotronics 2293 Automatic Transformer Winding Analyzer, 264VAC, 1kW

Electronic Test and Measurement Equipment

Hipotronics 2293 Automatic Transformer Winding Analyzer, 264VAC, 1kW Product Datasheet Download Product Datasheet

Rent Test Equipment

Product Overview

HAEFELY / HIPOTRONICS 2293 AUTOMATIC TRANSFORMER WINDING ANALYZER (Call for Availability)

The Haefely / Hipotronics 2293 Automatic Transformer Winding Analyzer uniquely combines winding resistance measurement, turns ratio measurement, core demagnetisation, transformer type detection and heat run test (cooling curve) in one extremely fast instrument. A simple one-time-connect-all system drastically reduces measureing time. Once connected all tests can be done in a row without any reconnection.

Features and Specifications of the Haefely / Hipotronics 2293 Automatic Transformer Winding Analyzer include:

Features:

  • Multipurpose winding analyzer - a transformer winding resistance, turns ratio, demagnetisation, type detection and heat run test (cooling curve) in one instrument
  • Setup is made easy with a simple one-time-connection system and once connnected will test all phases and windings
  • Each operation on touch screen interface with full graphical test visualization
  • Unique simultaneous winding magnetisation method for winding resistance measurements, equivalent to traditional equipment with up to 100 A test current
  • Advanced procedure for turns ratio and phase displacement measurement
  • Demagnetisation function - transformer is returned to a demagnetized status after measurement
  • Tap changer control signal 
  • Data transfer over USB memory-stick or LAN 
  • A valuable tool for factory test, acceptance test and regular maintenance on the following applications:
    • Power transformers
    • Distribution transformers
    • All types of HV windings

Specifications:

  • Resistance Measurement:  
    • Maximum Measuring Current DC:  32 A (user selectable)
    • Maximum Charging Voltage DC:  100 V  
    • Range:  0.1 μΩ - 300 kΩ
    • Accuracy: At temperature 0 to + 50ºC at highest available current
      • Resistance: 0.1 μΩ - 300 μΩ   Accuracy:  0.1% ± 0.5 μΩ 
      • Resistance: 300.1 µΩ - 30 kΩ   Accuracy:  0.1%
      • Resistance: 30.01 kΩ - 300 kΩ   Accuracy:  1%
  • Ratio Measurement:
    • Maximum Supply Current AC: 1 APeak/700mARMS
    • Maximum Measuring Voltage AC: 95 VPeak/67 VRMS  
    • Range:  1.0 - 100,000
    • Accuracy: At temperature 0 to + 50ºC at highest available current
      • Ratio: 1.0 - 100             Accuracy:  0.05% 
      • Ratio: 100 - 2,000          Accuracy:  0.1%
      • Ratio:  2,000 - 20,000     Accuracy:  1%
      • Ratio: 20,000 - 100,000   Accuracy:  5%
    • Phase (Ratio measurement)
    • Typical Accuracy: At 0 to + 50ºC at highest available voltage
      • Phase: 1.0 - 500       Typical Accuracy:  ±0.25° 
      • Phase: 500 - 10,000  Typical Accuracy:  ±1.00°
    • Phase (Clock number detection): 1.0 - 500  Accuracy (At 0 to + 50ºC at highest available voltage): ±0.05°
  • Mains Power Supply
    • Voltage:  90 VAC - 264 VAC
    • Maximum Power:  1000 W
    • Frequency:  47 Hz - 63 Hz

Request A Quote

Rent      Buy      Repair
SUBMIT REQUEST
760-806-6600


Testimonial







Home   |   Rental Equipment   |   Equipment Sales   |   Repair & Calibration   |   Sell Your Equipment   |   About Us   |   Contact   |   Get A Quote   |   Blog    



YouTube Facebook Google Plus Paypal
Get the latest deals first. Subscribe to our newsletter.    SUBSCRIBE


© 2020 Axiom Test, All Rights Reserved
FAQ      Privacy      Terms      Site Map      Site Map XML     
© 2020 Axiom Test, All Rights Reserved
FAQ      Privacy      Terms      Site Map      Site Map XML

Axiom Test Equipment
2610 Commerce Way Vista, CA 92081
Phone: (760) 806-6600